| The DP is the D-Series Regulator
with a corresponding spring controlled pressure pilot. It is used in steam pressure reducing applications requiring close accuracy with low to high capacity requirements. With a maximum inlet pressure of 250 psig, it controls downstream pressure between 3 and 200 psig using three color coded spring ranges. Also available is the P5 pilot capable
of controlling pressure to within 1/2 psig. |
Series DP with Class 250 Flanges |
 | Capacities: to 112,000 lbs/hr [50800 kg/hr] |
 | Maximum inlet pressure: 250 psig [17.2 bar] |
 | Reduced pressure range: 3 to 200 psig [0.2 to 13.8 bar] with 3
springs |
 | Sizes: 1/2", 3/4", 1", 1-1/4", 1-1/2",
2", 2-1/2", 3", 4", and 6" |
 | Connections:
 | NPT - 1/2" to 2" |
 | 125 lb Flg - 2" to 6" |
 | 250 lb Flg - 2" to 6" |
|
 | Material: Cast iron bodies with hardened stainless steel trim |
 | Weight: 18 to 600 lbs [8 to 270 kg] |
|
|
|
|
| The DT is the D-Series Regulator with a corresponding liquid filled temperature pilot. Typical applications include tank heating, steam coils, plating tanks, water heaters, steam chests, molds, and platens. The setpoint temperature is easily adjusted with the hand knob, and an internal bellows provides overheat protection. The pilot will control temperatures ranging from 60°F to 260°F in five overlapping ranges. |
Series DT |
 | Capacities: to 112,000 lbs/hr [50800 kg/hr] |
 | Maximum inlet pressure: 250 psig [17.2 bar] |
 | Temperature setting range: 60°F to 260°F (16°C - 127°C) |
 | Sizes: 1/2", 3/4", 1", 1-1/4", 1-1/2",
2", 2-1/2", 3", 4", and 6" |
 | Connections:
 | NPT - 1/2" to 2" |
 | 125 lb Flg - 2" to 6" |
 | 250 lb Flg - 2" to 6" |
|
 | Material: Cast iron bodies with hardened stainless steel trim |
 | Weight: 18 to 600 lbs [8 to 270 kg] |
|
|
|
|
| The DA is the D-Series Regulator with
a corresponding air controlled pilot for controlling pressure. Downstream pressure is maintained by delivering the proper air signal to the pilot. This air signal can be supplied to the valve from a remote location. Three signal
pressures to downstream pressure ratios are available for pressure ranges from 3 to 200 psi. |
Series DA, shown with a cutaway
pilot |
 | Capacities: to 112,000 lbs/hr [50800 kg/hr] |
 | Maximum inlet pressure: 250 psig [17.2 bar] |
 | Reduced pressure range: 3 to 200 psig [0.2 to 13.8 bar] with 3
pilots |
 | Sizes: 1/2", 3/4", 1", 1-1/4", 1-1/2",
2", 2-1/2", 3", 4", and 6" |
 | Connections:
 | NPT - 1/2" to 2" |
 | 125 lb Flg - 2" to 6" |
 | 250 lb Flg - 2" to 6" |
|
 | Material: Cast iron bodies with hardened stainless steel trim |
 | Weight: 18 to 600 lbs [8 to 270 kg] |
|
|
|
| The DS is the D-Series Regulator with a corresponding electrically actuated 120 volt solenoid pilot for on-off operation of the regulator. Normally the solenoid pilot is used in conjunction with a pressure or temperature pilot so that it is possible to enable or disable the steam system
with an electrical signal. Typical applications include automatic operations, remote control, programmed cycling, sequential function interlock, and emergency shut offs. |
Series DS |
 | Capacities: to 112,000 lbs/hr [50800 kg/hr] |
 | Maximum inlet pressure: 250 psig [17.2 bar] |
 | Sizes: 1/2", 3/4", 1", 1-1/4", 1-1/2",
2", 2-1/2", 3", 4", and 6" |
 | Connections:
 | NPT - 1/2" to 2" |
 | 125 lb Flg - 2" to 6" |
 | 250 lb Flg - 2" to 6" |
|
 | Material: Cast iron bodies with hardened stainless steel trim |
 | Weight: 18 to 600 lbs [8 to 270 kg] |
|
|
|
|
| The DBP is the D-Series Regulator with a corresponding spring controlled back pressure pilot. It is used to assure that a certain maximum set pressure will not be exceeded on the upstream side of the valve. If this maximum set pressure is reached the valve gently opens relieving the excess pressure. Not to be used in place of a safety relief valve. |
Series DBP |
 | Capacities: to 112,000 lbs/hr [50800 kg/hr] |
 | Inlet (back) pressure: 3 to 200 psig [0.2 to 13.8 bar] with 3
springs |
 | Sizes: 1/2", 3/4", 1", 1-1/4", 1-1/2",
2", 2-1/2", 3", 4", and 6" |
 | Connections:
 | NPT - 1/2" to 2" |
 | 125 lb Flg - 2" to 6" |
 | 250 lb Flg - 2" to 6" |
|
 | Material: Cast iron bodies with hardened stainless steel trim |
 | Weight: 18 to 600 lbs [8 to 270 kg] |
|
|
|
|
| The DPT is the Series D Regulator with both pressure and temperature pilots. This is a classic example of using two pilots in combination. The temperature pilot is used to control the process temperature. The pressure pilot is used to prevent the main valve from over pressurizing the downstream piping & components. |
 Series
DPT |
 | Capacities: to 112,000 lbs/hr [50800 kg/hr] |
 | Maximum inlet pressure: 250 psig [17.2 bar] |
 | Temperature setting range: 60°F to 260°F (16°C - 127°C) |
 | Reduced pressure range: 3 to 200 psig [0.2 to 13.8 bar] with 3
springs |
 | Sizes: 1/2", 3/4", 1", 1-1/4", 1-1/2",
2", 2-1/2", 3", 4", and 6" |
 | Connections:
 | NPT - 1/2" to 2" |
 | 125 lb Flg - 2" to 6" |
 | 250 lb Flg - 2" to 6" |
|
 | Material: Cast iron bodies with hardened stainless steel trim |
 | Weight: 18 to 600 lbs [8 to 270 kg] |
|
|